Duty |
80 Ampere Rating |
|
|
|
30% |
150 Amperes |
|
|
|
40% |
125 Amperes |
|
|
|
50% |
115 Amperes |
|
|
|
60% |
105 Amperes |
|
|
|
70% |
95 Amperes |
|
|
|
|
|
|
|
Typical Inductive fault Currents
Which can Be Ruptured (5ms Time Constant) |
|
|
|
|
|
Without Blowouts: |
500 Amperes at 48V DC |
|
|
|
With Blowouts: |
500 Amperes at 96V DC |
|
|
|
|
|
|
|
Maximum Recommended Contact Voltages
When Direct Current Loads Are To Be Switched |
|
|
|
|
| Without Blowouts: |
Inductive Load 48V |
Resistive Load 60V |
|
| With Blowouts: |
Inductive Load 96V |
Resistive Load 120V |
|
|
|
|
|
When loads are not switched even under
fault conditions, contact voltages
may be increased to 250V DC. |
|
|
|
|
|
|
Typical Voltage Drop Across
New Contacts: |
|
|
|
40mV at 80A |
|
|
| Mechanical Life: |
>3 x 10,000,000 |
|
|
| Coil Power Dissipation |
|
|
|
| Intermittently Rated Types
(50% Duty Cycle): |
10 to 14 Watts |
|
| Continuously Rated Types: |
5 to 7 Watts |
|
| Magnetically Latched Types: |
Initially 12 Watts (0.5Sec) |
|
|
|
Then 0 Watts |
|
| Maximum Pull-in Voltage (Coil at 20°C) |
|
|
| Intermittently Rated Types: |
60% V |
|
| Continuously Rated Types: |
66% V |
|
|
|
|
|
| Typical Drop-Out Voltage: |
10 to 25% |
|
| Typical Pull-in Time (N/O Contacts to
Close): |
15ms |
|
| Typical Drop-out Time (N/O Contacts to
Open) |
|
|
| Without Suppression: |
6ms |
|
| With Diode Suppression: |
35ms |
|
|
|
|
|
| Typical Main Contact Changeover Time (PC61
and SW61) |
|
| Normally Closed to Normally
Open: |
6ms |
|
| Normally Open to Normally
Closed: |
4ms |
|
|
|
|
|
| Typical Contact Bounce Period: |
3ms |
|
| Auxiliary Contact Thermal Current Rating: |
5 Amperes |
|
|
|
|
|
| Auxiliary Contact Switching Capacity
(Resistive Load): |
|
|
|
|
|
|
5A at 24V DC |
1A at 60V DC |
|
|
O.5A at 120V Dc |
0.25A at 240V DC |
|
|
|
|
|
|