SW1500
Heavy Duty D.C. Contactor
for Telecommunication & Power Centres

Page Links

 

 
   
   
     
     

SW1500 Heavy Duty D.C. Contactor

Bus Bar Mounting Product Range Designed for Telecommunication and Power Distribution.


The following contactor is supplied with flat bar style fixed contacts, as opposed to the traditional stud termination. The contactor can be mounted solely to bus bar connections, or tapped magnet frames allow for panel or bracket mounting.
 

Unique Range
This contactor has been designed for direct current loads but can also be used for Alternating currents. The contact tips are silver alloy which is weld resistant, hard wearing and has very good conductivity. This contactor is compact in size and is fully serviceable, with a complete range of spare parts available.

Operating Coils
Coil voltages ranging from 6 to 240 are available and these are wound for DC operation. However, coils can be fitted with a Bridge Rectifier for use from A.C. supplies. Coils are wound for continuous duty.

Pull-in voltages (coils at 20°C) are approximately 66% of the rated voltage. Drop-out voltage is nominally greater than 10% of rated voltage. Variations from these pull-in and drop-out figures can be engineered to suit particular applications. Coil connections are by means of 6.3mm spades.

Auxiliary Contacts
A double circuit normally open, normally closed microswitch can be fitted to the contactors. This has a D.C. resistive rating of 5 amperes at 24 volts. The suffix "A" should be added to the type number when auxiliary contacts are needed, for example SW1500A.

 

 

 

Please Note: The Thermal Current ratings stated for the contactors are dependent upon the correct size of busbar being used for the required duty. For maximum continuous ratings the busbars should not be less than the sizes shown in the drawings below.

The contactors can be mounted vertically or horizontally. If mounted vertically the coil should be at the bottom. All performance data shown should be used as a guide only. Alternative ratings may be considered according to applications.

 

Performance Data

 

   

Thermal Current Rating (100%):

  1500 Amperes

 

Overload Currents that can be ruptured (in accordance with UL508)

Resistive Load:

  2250 amperes at 60V D.C.
     

Maximum Recommended Contact Voltage:

  60V D.C.
 
Typical Voltage Drop across Contacts  

per 100 amperes:

  15mV
     

Mechanical Life:

  >1,000,000 operations
     

Coil Power Dissipation:

  25 to 35 watts
     
Maximum Pull-in Voltage (coil at 20°C)

Continuously Rated:

  66% of rated voltage
     

Typical Drop-out voltage:

  >10% of rated voltage
     
Typical Pull-in Time    

normally open contacts to close:

  80mS
     
Typical Drop-out Time (normally open contacts to open)

Without Suppression:

  15mS

With Diode Suppression:

  120mS

With Diode and resistor (value dependent):

  30mS
     
Auxiliary Contact Switching Capacities    

Resistive Load:

  5A at 24V D.C.
    2A at 48V D.C.
    0.5A at 240V D.C.
     
Weight    

SW1500:

  3950 grams

SW1500A:

  3970 grams
 

SW1500 Dimensions

 

 

 

LG Industrial Systems Benedikt Jager Broyce Control Controls Switchgear
Albright International UK Vishay Germany Rudolf PFC Modules