Control Relays |
Type 45TCR
PT100 Temperature Control Relay |
| Page Links |
Page Bookmarks |
|
|
|
|
|
|
 |
 |
 |
|
| |
|
 |
|
|
|
 |
|
Control Relay Type 45TCR
|
45 Series Din Rail Mtg |
|

Dims: (mm)
H.78 x W.45 x D.99 |
Type No. |
45TCR |
|
Function |
Monitoring or Control of Temperature |
| |
- |
|
|
- |
| |
- |
|
Hysteresis |
0.5 to 20% |
|
Analog Output |
0 to 10V DC |
|
Output |
SPDT Relay |
|
Output Rating |
8A @ 250V AC |
|
Supply Voltage Un |
24V DC |
| |
24V, 115V AC |
|
|
24C, 230V AC |
|
Integral Transformer |
Yes |
|
Monitoring Range |
-50°C to 300°C |
| |
- |
|
Type 45TCR
Mounting Diagram |
Type 45TCR
Connection Diagram |

Insert screwdriver to release clip |
 |
|
Installation/Data Sheet Supplied
Note: The relay is shown in the de-energised condition.
Installation and Setting
* Connect
the Unit as shown in the diagram. (Ensure the correct terminals are used
when connecting to the supply).
* Select the required temperature range. (N.B. fit link between terminals
'Y1' and 'Z' for 200 to 300°C range).
* Set the relay inversion switch to either 'N' (Normal) or 'I' (Inverted).
* Apply power (green LED on).
Analogue Outputs
* Connecting between terminals 'Y1' and
'X1' provides DC voltage relative to the set point
(i.e. set point @ 20% = 2V DC out).
* Connecting between terminals 'Y1' and 'X2' provides DC voltage relative
to the measured temperature within any range selected. |
|
Specifications Type No. 45TCR Control Relay |
|
Supply Voltage Un: |
24V DC |
| |
24V, 115V AC 45 to 65Hz* |
| |
24V, 230V AC 45 to 65Hz* |
| |
*Integral Transformer |
|
|
- |
|
Supply Variation: |
85 to 115% of Un |
Isolation:
|
3.75kV (N.B. There is no isolation between input and
analogue output). |
|
Power Consumption: |
≈ 4.5VA (27.6V AC), 4.8VA (264V AC) |
|
( @ 115% X Un) |
≈ 1W (27.6V DC) |
| |
- |
|
Input: |
PT100 2 or 3-wire (to DIN 43760) |
|
Temperature Ranges: |
-50°C to +50°C, 0°C to
50°C, 0°C to 100°C, |
|
|
(selectable) 100°C to 200°C,
200°C to 300°C |
|
Set Point: |
0 to 100% of selected temperature range |
|
Hysteresis: |
0.5 to 20% |
|
Temperature Drift: |
0.05% per °C (maximum) |
|
Time Delay: |
200mS (worst case 5 x t) |
| |
- |
|
Output: |
1 x SPDT |
|
Output Rating: |
AC1 250V AC 8A
(2000VA) |
| |
AC15 250V AC 5A (no), 3A
(nc) |
| |
DC1 25V DC 8A
(200W) |
| |
- |
|
Analogue Output: |
0 to 10V DC (relative to set point or measured
temperature) |
| |
Imax = 2mA R
load ≥5KΩ |
| |
- |
|
Mounting Option: |
On to 35mm symmetric DIN rail to BS5584:1978 |
| |
(EN50 002, DIN 46277-3) |
|
Terminal Conductor Size: |
≤ 2 x 1.5mm²
stranded wire |
| |
≤ 2 x 2.5mm²
solid wire |
| |
- |
|
Electrical Life: |
≥150,000 ops at rated load |
|
Ambient Temperature: |
-20°C to +50°C |
|
Relative Humidity: |
+95% |
|
Housing: |
to UL94 VO |
|
Weight |
≈ 200g |
|
Conforms To: |
UL, CUL, CSA & IEC |
|
Approvals: |
CE Compliant |
| The information provided is believed to be accurate (
subject to change without prior notice); however, use of such information
shall be entirely at the user's own risk. |
|
 |
|