Three-Phase Relays |
Type B1PRC Phase Failure/ Under & Over
Voltage Plus Time Delay
Type B1PRC-4W Phase Failure/ Under & Over
Voltage Plus Time Delay |
| Page Links |
Page Bookmarks |
|
|
|
|
|
|
 |
 |
 |
 |
| |
|
 |
 |
|
|
|
|
3-Phase Relay Types B1PRC and
B1PRC-4W
|
B1 Series 11 Pin Plug-In Three-Phase Relays |
|

Dims: (mm)
H.80 x W.40 x D.92 |
Type No. |
B1PRC |
B1PRC-4W |
| Function |
Voltage |
Voltage |
|
Under / Over Voltage |
Under and Over |
Under and Over |
|
Adjustable Trip Level |
Yes |
Yes |
|
Phase Loss (Failure) |
Yes |
Yes |
|
Neutral Loss |
No |
Yes |
|
Phase Sequence (Rotation) |
No |
No |
|
Phase Asymmetry |
No |
No |
Time Delay
(from
fault) |
0.2 to 10 seconds |
0.2 to 10 seconds |
| Output |
1 x SPDT Relay |
1 x SPDT Relay |
| Output Rating |
10A @ 250V AC |
10A @ 250V AC |
| Integral
Transformer |
Yes |
Yes |
| Supply Voltage
Un |
220, 380, 400, 415, 480V AC |
220, 380, 400, 415V AC |
| |
- |
- |
| Monitoring
Range |
Monitors own Supply |
Monitors own Supply |
|
Specifications Type No. B1PRC Three-Phase Relay |
|
Supply / Monitoring Voltage Un: |
230, 380, 400, 415, 480V AC, 45 to 65Hz
(80 to 120% of Un) |
| |
- |
|
Trip Levels: |
Lower: 85 to 95%. Upper: 105 to
115% (of Un) |
| |
- |
|
Power Consumption: |
≈ 8VA (red and blue phases) |
| |
≈ 1VA (yellow phase) @ 120% of Un |
|
|
- |
|
Isolation: |
Over voltage CAT. III (IEC 60664) |
|
Rated Impulse / Withstand Voltage |
4kV (1.2 / 50µS |
| |
- |
|
|
- |
|
Hysteresis: |
< 2% |
|
Time Delay: |
0.2 to 10 seconds (-10/+30% on max.) |
| |
- |
|
Contact Rating: |
1 x SPDT |
| |
AC1 250V AC / 10A (2500VA) |
| |
AC15 250V AC / 6A |
| |
DC1 25V DC / 10A (250W) |
|
Electrical Life: |
Minimum 150,000 ops at rated load |
|
Ambient Temperature: |
-20°C to +60°C |
|
Relative Humidity: |
+95% |
|
Housing |
Flame Retardant UL94 VO |
|
Weight |
≈ 250g |
|
Conforms To: |
UL 508, CSA 22.2 / 14, IEC 60664, IEC 60947 |
|
Approvals: |
CE Compliant |
|
Specifications Type No. B1PRC-4W (4 Wire) Three-Phase Relay |
|
Supply / Monitoring Voltage Un: |
230, 380, 400, 415V AC, 45 to 65Hz
(80 to 120% of Un) |
| |
- |
|
Trip Levels: |
Lower: 85 to 95%. Upper: 105 to
115% (of Un) |
| |
- |
|
Power Consumption: |
≈ 8VA (red and blue phases) |
| |
≈ 1VA (yellow phase) @ 120% of Un |
|
|
- |
|
Isolation: |
Over voltage CAT. III (IEC 60664) |
|
Rated Impulse / Withstand Voltage |
4kV (1.2 / 50µS |
| |
- |
|
|
- |
|
Hysteresis: |
< 2% |
|
Time Delay: |
0.2 to 10 seconds (-10/+30% on max.) |
| |
- |
|
Contact Rating: |
1 x SPDT |
| |
AC1 250V AC / 10A (2500VA) |
| |
AC15 250V AC / 6A |
| |
DC1 25V DC / 10A (250W) |
|
Electrical Life: |
Minimum 150,000 ops at rated load |
|
Ambient Temperature: |
-20°C to +60°C |
|
Relative Humidity: |
+95% |
|
Housing |
Flame Retardant UL94 VO |
|
Weight |
≈ 250g |
|
Conforms To: |
UL 508, CSA 22.2 / 14, IEC 60664, IEC 60947 |
|
Approvals: |
CE Compliant |
|