Control Relays

B1UCS  Detects Under Current
B1OCS  Detects Over Current

 

Page Links Page Bookmarks
   

 

Control Relay Types B1UCS and B1OCS


 

B1 Series 11 Pin Plug-In Control Relays

Dims: (mm)
H.80 x W.40 x D.92

Type No. B1UCS B1OCS
Function Under Current Over Current
  - -
Time Delay (from
fault)
˝1 second ˝1 second
  - -
Hysteresis ˝1% ˝1%
Latch No No
Output SPDT Relay SPDT Relay
Output Rating 8A @ 250V AC 8A @ 250V AC
Supply Voltage Un 12, 48V AC/DC, 24V DC 12, 48V AC/DC, 24V DC
  24, 110, 220/240V AC 24, 110, 220/240V AC
  110, 220/240V AC Only 110, 220/240V AC Only
  - -
Integral Transformer 0.35 to 5A AC 0.35 to 5A AC
Monitoring Range 0.5 to 7.5A DC 0.5 to 7.5A DC

 

How to order: Please quote Type Number, Voltage and Quantity
Type No. B1UCS Connection Diagram

Installation Data Sheet Supplied

Note: This Relay is shown in the
         de-energised condition.

Note: 12, 24 and 48 Volt Units are not
          isolated between Monitored & Supply Input.

 

B1UCS Key Features Function Diagram
Detects Under Current Condition
Adjustable Trip Level
SPDT Relay Output 8A
Plug-In
Led Indication
-
-

 

Specifications Type No. B1UCS  Control Relay

Supply Voltage Un: 12, 24, 48V DC
  12, 24, 48, 110, 230V AC, 48 to 63Hz
  (85 to 110% of Un)
  -
Power Consumption: 3VA @ Un
  -
Monitoring Range: AC: 0.35 to 5A 
  DC: 0.5 to 7.5A
  -
  -
Accuracy: ± 0.5% at constant conditions
Hysteresis: Factory Set 1%
Time Delay: t = 1 second, worst case 3 x t
  -
Contact Rating: 1 x SPDT
  AC1   250V AC/8A (2000VA)
  AC15 250V AC/2.5A
  DC1   24V DC/8A  (200W)
Electrical Life: Minimum 150,000 ops at rated load
Ambient Temperature: -20 to +60°C
Relative Humidity: +95%
Housing Flame Retardant UL94 VO
Weight ≈180g
Conforms To: UL 508, CSA 22.2/14, IEC 1010
Approvals: CE Compliant

 

How to order: Please quote Type Number, Voltage and Quantity
Type No. B1OCS Control Relay Connection Diagram

Installation Data Sheet Supplied

Note: This Relay is shown in the de-energised
          condition.

Note: 12, 24 and 48 Volt Units are not isolated
          between Monitored & Supply Input.

B1OCS Key Features Function Diagram
Detects Over Current Condition
Adjustable Trip Level
SPDT Relay Output 8A
Plug-In
LED Indication
-
-

 

Specifications Type No. B1OCS  Control Relay

Supply Voltage Un: 12, 24, 48V DC
  12, 24, 48, 110, 230V AC, 48 to 63Hz
  (85 to 110% of Un)
  -
Power Consumption: 3VA @ Un
  -
Monitoring Range: AC: 0.35 to 5A 
  DC: 0.5 to 7.5A
  -
  -
Accuracy: ± 0.5% at constant conditions
Hysteresis: Factory Set 1% (externally adjustable)
Time Delay: t = 1 second, worst case 3 x t
  -
Contact Rating: 1 x SPDT
  AC1   250V AC/8A (2000VA)
  AC15 250V AC/2.5A
  DC1   24V DC/8A  (200W)
Electrical Life: Minimum 150,000 ops at rated load
Ambient Temperature: -20 to +60°C
Relative Humidity: +95%
Housing Flame Retardant UL94 VO
Weight ≈180g
Conforms To: UL 508, CSA 22.2/14, IEC 1010
Approvals: CE Compliant

 

LG Industrial Systems Benedikt Jager Broyce Control Controls Switchgear
Albright International UK Vishay Germany Rudolf PFC Modules