Broyce ELRF Earth Leakage Relay
 







Earth Leakage Relays

Fixed Types (Type A)

Page Links

Page Bookmarks

Accessories
     

Earth Leakage Relays (Fixed) Type A
ELRF0030, 0100 and 0300
 

Type ELRF Earth Leakage Relay (Fixed) - Type A

Dims: (mm)
H.85 x W.70 x D.63.5

Type No ELRF0300 ELRF0100 ELRF0030
Function Fixed - Type A Fixed - Type A Fixed - Type A
Supply Voltage Un 110, 115, 220/240V
AC 50/60Hz
110, 115, 220/240V
AC 50/60Hz
110, 115, 220/240V
AC 50/60Hz
Sensitivity IΔn 300mA 100mA 30mA
Range - - -
Time Delay Instantaneous Instantaneous Instantaneous
LED Indication Tripped indication Tripped indication Tripped indication
  - - -
  - - -
Test/Reset Facility Local Only Local Only Local Only
Output SPDT Relay SPDT Relay SPDT Relay
Output Rating 8A @ 250V AC 8A @ 250V AC 8A @ 250V AC
50% Fault Level Output - - -
Adjustment Cover and Tamperproof Seal No No No
Ratio - - -
Internal Dimension - - -

 

Type ELRF Key Features
Designed to monitor and detect earth currents using separate toroid.
Fixed sensitivity of 30mA, 100mA or 300mA
"Test" button for simulation of fault condition.
"Reset" button for clearing of fault condition.
SPDT relay output
LED indication of fault condition after unit has tripped.

 

Function Diagram

 

How to order: Please quote Type Number, Voltage and Quantity

Type ELRF Connection Diagram

Installation and Setting

* Before Installation, Isolate the Supply.

  • Connect the unit as shown in the diagram above.
  • Apply power. The output  relay will remain de-energised.
  • The output relay will energise if:

          (a) The fault current level exceeds the fixed trip level (IΔn)
          (b) There is a failure of the connection between the relay and the toroid

Fault Simulation

  • Pressing the "Test" button allows a fault to be simulated. The output relay will operate accordingly.
  • Pressing the "Reset" button after a fault has occurred restores the unit back to its normal operation. (Note that the relay can also be reset by removing then re-applying the supply).

Note: The operating function of this unit is classed as a Type A  for which tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether applied suddenly or slowly rising. Additionally, this unit is protected against nuisance tripping

Type ELRF Mounting Details

 

 

Specifications Type No. ELRF Series Earth Leakage Relay

Supply Voltage Un: 220/240V AC, 50/60Hz
Residual Voltage: 500V AC maximum
Supply Variation: 90 to 110% of Un
Isolation: Over Voltage CAT III
Power Consumption: ≈ 5VA
   
Sensitivity IΔn (mA): 30,100 or 300mA (Note:*see below)
Range: -
Time Delay: Instantaneous
 

-

Memory: Storage of the leakage fault and reset with "reset" button.
Toroid withstand capacity: 50kA for 200mS
Distance between Toroid and Relay: 50 meters (max.)
Ambient Temperature: -5°C to +60°C
  -5°C to +40°C (in accordance with IEC 60755)
Relative Humidity: +95%
   
Output: SPDT Relays
Output Rating: AC1    250V AC,  8A  (2000VA)
  AC15  250V AC,  2.5A
  DC1    25V DC,    8A  (200W)
Electrical Life: ≥ 150,000 ops at rated load
Fault Level Output: 10W max. (resistive) @ Un (50% of IΔn)
Housing Grey Flame Retardant Lexan UL94 VO
Weight ≈ 190g
Mounting Option: On to 35mm symmetric DIN Rail to BS5584:1978
  (EN50 002, DIN 46277-3)
Terminal Conductor Size: ≤ 2.5mm² stranded
  ≤ 4mm² solid
Conforms To: IEC 60755, 50081-1, 50081-2, 50082-1 and 50082-2
Approvals: CE Compliant

Note: *
Please state sensitivity when ordering. The suffix which should follow ELRF is 0030
(30mA),         0100 (100mA) or 0300 (300mA).  Example: ELRF-0300
 

 

Accessories
Toroids:

 

 

 

BZCT035 - 35mm
BZCT070 - 70mm
BZCT120 - 120mm
Note: The 120mm Toroid Is Not suitable for use with 30mA and 100mA units.

 

 