Earth Leakage Relay Type ELRV-10

 

 

ELRV Series Din Rail Mtg Earth Leakage Relay

Dims: (mm)
H.85 x W.70 x D.63.5

Type No.

ELRV-10

Function Variable - Type A
Supply Voltage Un 220 to 240V AC,   50 to 60Hz
Sensitivity IΔn 30, 50, 75, 100mA (selectable)
Range x1, x10, x100  (selectable)
Time Delay Inst., 50, 250, 500mS
LED Indication Tripped Indication
  Bargraph Indicating
  % of Leakage Current
Test/Reset Facility Local and Remote
Output 2 x SPDT Relays
Output Rating 8A @ 250V AC
50% Fault Level Output 10W maximum @ Un
Adjustment Cover and Tamperproof Seal Yes
Ratio -
  -
Internal Dimension -
External Dimension -

 

Type ELRV-10 Key Features
Designed to monitor and detect earth fault currents using separate toroid
Selectable sensitivity and time delay with tamper proof cover
"Test Button" for simulation of fault condition
"Reset Button" for clearing of fault condition
Remote operation of "Test" and "Reset" buttons
2 x SPDT relay output - Standard output and positive safety output
LED scale display of fault level prior to tripping

 

How to order: Please quote Type Number, Voltage and Quantity

Type ELRV-10 Function Diagram

 

 

Type ELRV-10 Connection Diagram

Installation and Setting
  • Before Installation, Isolate the Supply.
  • Connect the unit as shown in the diagram above (N.B. certain features may not be required and therefore do not need to be connected).
  • Apply power and the "Positive Safety Output" relay will energise. The relay will de-energise if:

          (a) The fault current level exceeds the set trip level (IΔn)*
          (b) There is a failure of the connection between the relay and the toroid*
          (c) The supply to the relay is removed.
          (d) The relay fails internally.

          (*) Causes the "standard output" relay to energise in response to the fault condition.

  • Prior to a fault occurring, the LED level display will indicate the % of IΔn being detected (the display is scaled between 5, 15, 30, 45, 60 and 75% of the set trip level). After all 5 LED's have illuminated and the unit trips due to an excessive fault current, the red LED will illuminate.
  • For remote indication of a fault occurring (when IΔn is @ 50% a lamp or similar indicating device can be connected between terminals "1" and "2".

Note: The operating function of this unit is classed as a Type A  for which tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether applied suddenly or slowly rising. Additionally, this unit is protected against nuisance tripping

Type ELRV-10 Mounting Details

 

Specifications Type No. B1CVR  Control Relay

Supply Voltage Un: 220/240V AC, 50/60Hz
Residual Voltage: 500V AC maximum
Supply Variation: 90 to 110% of Un
Isolation: Over Voltage CAT III
Power Consumption: ≈ 5VA
   
Sensitivity IΔn (mA): 30*, 50, 75, 100 mA  (selectable)
Range: x1*, x10, x100  (selectable)
Time Delay (t) : Instantaneous*, 50, 250, 500mS  (selectable)
 

Note: The unit is factory set to 30mA trip and instantaneous delay. Adjustments of these settings is prevented by the tamperproof cover, which is sealed at the factory. Access to the adjustments can only be made once the factory seal is broken. A spare seal is supplied with the unit and should be fitted if any adjustments are made.

Memory: Storage of the leakage fault and reset with "reset" button.
Toroid withstand capacity: 50kA for 200mS
Distance between Toroid and Relay: 50 meters (max.)
Ambient Temperature: -5°C to +60°C
  -5°C to +40°C (in accordance with IEC 60755)
Relative Humidity: +95%
   
Output: 2 x SPDT Relays
Output Rating: AC1    250V AC,  8A  (2000VA)
  AC15  250V AC,  2.5A
  DC1    25V DC,    8A  (200W)
Electrical Life: ≥ 150,000 ops at rated load
Fault Level Output: 10W max. (resistive) @ Un (50% of IΔn)
Housing Grey Flame Retardant Lexan UL94 VO
Weight ≈ 200g
Mounting Option: On to 35mm symmetric DIN Rail to BS5584:1978
  (EN50 002, DIN 46277-3)
Terminal Conductor Size: ≤ 2.5mm² stranded
  ≤ 4mm² solid
Conforms To: IEC 60755, 50081-1, 50081-2, 50082-1 and 50082-2
Approvals: CE Compliant

 

Accessories
Toroids:

 

 

 

BZCT035 - 35mm
BZCT070 - 70mm
BZCT120 - 120mm
BZCT210 - 210mm
Note: The 120 and 210mm Toroids MUST NOT be used if sensitivity settings of less than 300mA are required.
 

 