BS Pattern Catalog No. |
ETSF32GI |
ETSF63GI |
|
|
|
| Rated Insulation Voltage |
|
|
750V |
750V |
|
|
|
|
|
| Rated thermal current & operational |
In free air |
660V |
32A |
63A |
| current AC22 Ambient temp. 40°C
|
In enclosure (no
ventilation) |
660V |
32A |
63A |
|
free mounting position. note (1) |
In enclosure (solid links) |
660V |
40A |
75A |
|
|
|
|
|
|
| Rated Operational voltage |
|
|
|
500V |
660V |
|
|
|
|
|
|
| Rated operational current in categories |
|
|
220V |
32A |
63A |
| AC23 and AC3. Time interval between |
|
|
380V |
32A |
63A |
| operations 20 seconds in AC3. |
|
|
415V |
32A |
63A |
| |
|
|
660V |
- |
40A |
|
|
|
|
|
|
| Rated operational current DC23 |
Two poles in series |
110V |
- |
63A |
| |
Two poles in series |
220V |
- |
63A |
| |
Three poles in series |
440V |
- |
30A |
|
|
|
|
|
|
| Rated operational power in categories |
|
220V |
7.5kW |
15kW |
| AC23 and AC3. Time interval |
|
|
380V |
11kW |
30kW |
| between operations |
|
|
415V |
15kW |
30kW |
| 20 seconds in AC3
note (2) |
|
|
500V |
15kW |
30kW |
| |
|
|
660V |
- |
30kW |
|
|
|
|
|
|
| Rated breaking capacity |
|
|
500V |
300A |
500A |
| AC23.COSø
= 0.35 |
|
|
660V |
- |
350A |
|
|
|
|
|
|
| Rated breaking capacity |
|
|
110V |
- |
300A |
| DC, L/R = 15mS |
|
|
220V |
- |
250A |
| |
|
|
440V |
- |
- |
|
|
|
|
|
|
| Rated fused short circuit
current |
R.M.S. |
value |
500V |
50kA |
50kA |
| and making capacity on |
Peak |
value |
500V |
105kA |
105kA |
| fault level ......... |
R.M.S. |
value |
660V |
50kA |
50kA |
| |
Peak |
value |
660V |
105kA |
105kA |
|
|
|
|
|
|
| ........with back up fuses
of rating |
|
|
|
35A |
63A |
| Maximum peak let through
current |
|
|
660V |
6kA |
10KA
(4) |
| Rated short-time withstand
current 1sec |
|
|
660V |
15kA |
2kA |
| Rated capacitor power
note (3) |
|
|
380V |
15kVAr |
30kVAr |
| |
|
|
415V |
16kVAr |
32kVAr |
|
|
|
|
|
|
| Mechanical / Electrical
endurance |
|
3-pole switch
fuses |
20000/1500 |
20000/1500 |
| at rated current PF
0.65 |
|
|
|
operations |
operations |
|
|
|
|
|
|
| Fuse types BS pattern |
|
BS88 |
|
A2-A3 |
A2-A3 |
| distance of fixing holes |
|
|
|
73mm |
73mm |
|
|
|
|
|
|
|
Weight |
|
3-pole switch fuses |
1.6kg |
1.6kg |
|
|
|
|
|
|
| Notes: |
| |
(1) |
Ambient temperature 60°C,
derating 20% mounting on 'ceiling', |
| |
|
derating 10% on 'wall',
horizontal 8%. |
| |
(2) |
Some fuse links limit these
figures further. Starting current characteristics |
| |
|
must be considered separately. |
| |
(3) |
The capacitor rating of the
switch fuse is limited by the fuse link. |
| |
(4) |
UC-415V at 660V max peak
let through is 8kA. |
|