Controls and Switchgear Switch Fuses 2
 







CONTROLS & SWITCHGEAR  



Switch Fuses 125 to 200

Page Links      
   
   
   
   
     

ASTA Certified to
IEC 947-3

Tested by TCA
Lane Cove, Sydney

Switch Sizes Size 125 Size 200
BS Pattern Catalog No. ETSF100GI ETSF200B3
Rated Insulation Voltage 750V 750V
Rated thermal current & operational In free air 660V 125A 200A
current AC22 Ambient temp. 40°C In enclosure (no ventilation) 660V 115A 200A
free mounting position.  note (1) In enclosure (solid links) 660V 125A 280A
Rated Operational voltage 660V 660V
Rated operational current in categories     220V 115A 200A
AC23 and AC3. Time interval between     380V 115A 200A
operations 20 seconds in AC3.     415V 115A 200A
      660V 115A 200A
Rated operational current DC23 Two poles in series 110V 63A 200A
  Two poles in series 220V 125A 200A
  Three poles in series 440V 100A 200A
   
Rated operational power in categories   220V 37kW 57kW
AC23 and AC3. Time interval     380V 55kW 100kW
between operations     415V 60kW 110kW
20 seconds in AC3  note (2)     500V 75kW 140kW
     

660V

55kW 180kW
Rated breaking capacity     500V 800A 3200A
AC23.COSø = 0.35     660V 500A 3200A
Rated breaking capacity     110V 500A 1600A
DC, L/R = 15mS     220V 400A 1200A
      440V - 1200A
Rated fused short circuit current R.M.S. value 500V 80kA 100kA
and making capacity on Peak value 500V 175kA 220kA
fault level ......... R.M.S. value 660V 50kA 100kA
  Peak value 660V 105kA 220kA
........with back up fuses of rating       125A 200A
Maximum peak let through current     660V 18kA 40KA
Rated short-time withstand current 1sec     660V 5kA 8kA
Rated capacitor power  note (3)     380V 50kVAr 90kVAr
      415V 55kVAr 100kVAr
Mechanical / Electrical endurance   3-pole switch fuses 15000/1000 10000/1000
at rated current  PF 0.65       operations operations
Fuse types BS pattern   BS88   A2-A4 B1-B2
distance of fixing holes       94mm 111mm
Weight   3-pole switch fuses 2.1kg 6.9kg
Notes:
  (1) Ambient temperature 60°C, derating 20% mounting on 'ceiling',
    derating 10% on 'wall', horizontal 8%.
  (2) Some fuse links limit these figures further. Starting current characteristics
    must be considered separately.
  (3) The capacitor rating of the switch fuse is limited by the fuse link.
   

 