Controls and Switchgear Switch Fuses 3
 







CONTROLS & SWITCHGEAR  



Switch Fuses 315 to 400

Page Links      
   
   
   
   
     

ASTA Certified to
IEC 947-3

Tested by TCA
Lane Cove, Sydney

 
Switch Sizes Sizes 315 and 400
BS Pattern Catalog No. ETSF315B3 ETSF400B3
Rated Insulation Voltage 750V 750V
Rated thermal current & operational In free air 660V 315A 400A
current AC22 Ambient temp. 40°C In enclosure (no ventilation) 660V 290A 345A
free mounting position.  note (1) In enclosure (solid links) 660V 400A 450A
Rated Operational voltage 660V 660V
Rated operational current in categories     220V 315A 400A
AC23 and AC3. Time interval between     380V 315A 400A
operations 20 seconds in AC3.     415V 315A 400A
      660V 315A 400A
Rated operational current DC23 Two poles in series 110V 315A 400A
  Two poles in series 220V 315A 400A
  Three poles in series 440V 300A 400A
Rated operational power in categories   220V 90kW 110kW
AC23 and AC3. Time interval     380V 160kW 210kW
between operations     415V 180kW 230kW
20 seconds in AC3  note (2)     500V 220kW 280kW
     

660V

290kW 330kW
Rated breaking capacity     500V 3200A 3200A
AC23.COSø = 0.35     660V 3200A 3200A
Rated breaking capacity     110V 1600A 1600A
DC, L/R = 15mS     220V 1600A 1600A
      440V 1600A 1600A
Rated fused short circuit current R.M.S. value 500V 100kA 100kA
and making capacity on Peak value 500V 220kA 220kA
fault level ......... R.M.S. value 660V 100kA 50kA
  Peak value 660V 220kA 105kA
........with back up fuses of rating       315A 400A
Maximum peak let through current     660V 45kA 45KA
Rated short-time withstand current 1sec     660V 10kA 10kA
Rated capacitor power  note (3)     380V 145kVAr 180kVAr
      415V 160kVAr 200kVAr
Mechanical / Electrical endurance   3-pole switch fuses 10000/1000 10000/1000
at rated current  PF 0.65       operations operations
Fuse types BS pattern   BS88   B1-B3 B1-B4
distance of fixing holes       111mm 111mm
Weight   3-pole switch fuses 7.3kg 7.8kg
Notes:
  (1) Ambient temperature 60°C, derating 20% mounting on 'ceiling',
    derating 10% on 'wall', horizontal 8%.
  (2) Some fuse links limit these figures further. Starting current characteristics
    must be considered separately.
  (3) The capacitor rating of the switch fuse is limited by the fuse link.
   