ETS Power Factor Correction Modules
 







Power Factor Correction Modules

Page Links

  Page Bookmarks  
   
   
     
     

 

  Pre-Engineered Modules
 
 

For the convenience of the switchboard builder and OEM customer, a range of easy-to-install modules containing capacitors, contactors, busbar mounted fuses and busbars for connecting multiple modules together have been developed and are available for installation into existing cubicles.

 

Available Types

 

 Dimensions

 

  • Suitable for inclusion into a standard 400mm deep x 600mm wide switchboard.

Modules measure:
           430mm (H) x 510mm (W) x 370mm (D)

 

 


 

 

 

 

 


 

  • 50kVAr    in 2 x 25kVAr steps.
  • 100 kVAr in 1 x 50 plus 2 x 25 kVAr steps.
  • 150kVAr  in 3 x 50 kVAr steps.

Ordering Code

  • Module with 440V capacitors suitable for use with reactors use Part No ELE131440/...kVAr
  • Module with 525V capacitors suitable for use with reactors use Part No ELE1315251/...kVAr

 

Calculations and Tables

 

Target Power Factor
Actual
Power
Factor
0.70 0.75 0.80 0.85 0.90 0.92 0.94 0.96 0.98 1.00
0.40 1.27 1.41 1.54 1.67 1.81 1.87 1.93 2.00 2.09 2.29
0.45 0.96 1.10 1.23 1.36 1.50 1.56 1.62 1.69 1.78 1.98
0.50 0.71 0.85 0.98 1.11 1.25 1.31 1.37 1.44 1.53 1.73
0.55 0.50 0.64 0.77 0.90 1.03 1.09 1.16 1.23 1.32 1.52
0.60 0.31 0.45 0.58 0.71 0.85 0.91 0.97 1.04 1.13 1.33
0.65 0.15 0.29 0.42 0.55 0.68 0.74 0.81 0.88 0.97 1.17
0.70 0.00 0.14 0.27 0.40 0.54 0.59 0.66 0.73 0.82 1.02
0.75 0.00 0.13 0.26 0.40 0.46 0.52 0.59 0.68 0.88
0.80 0.00 0.13 0.27 0.32 0.39 0.46 0.55 0.75
0.85 0.00 0.14 0.19 0.26 0.33 0.42 0.62
0.90 0.00 0.06 0.12 0.19 0.28 0.48
The required capacitor output may be calculated as follows:
  • Determine the factor "k" by matching the point where actual and target power factor intersect.
  • Calculate the required capacitor rating with the formula Qc =k x P
    Example

    Actual power factor = 0.70, Target power factor = 0.96, Real power (P) = 35kW

    Capacitor output (Qc) = k x P
                                  
 = 0.73 x 35kW
                              Q
c   = 25.5 kVAr

 

   