LG Adjustable MCCBs 1200AF E-Trip
 







Adjustable MCCBs Electronic Trip ABS types
Page Links Thermal-magnetic trip Electronic trip
     
     
       
     
         
  Auxiliaries Manual Rotary Handles
     
     

Adjustable MCCBs Frame Size 1200AF Electronic Trip

 

Electronic trip
  Rated current, In 800, 1200A
Type of trip unit Electronic trip with LSIA configuration
   1. Long time pick-up, Ir (0.5-0.6-0.7-0.8-0.9-1.0) x In ..adjustable via knob
   2. Short time pick-up, Im (2-3-4-5-6-8-10) x Ir ....adjustable via knob
   3. Short time delay, tm 0.1 - 0.2 - 0.3 seconds ...adjustable
Instantaneous pickup 11 x In ...fixed
   4. Rated frequency 50 - 60Hz selectable by switch on trip unit.
   5. Alarm Warning via LED flickering when the load
  current is between 70 to 110% of set current Ir.
  LED stays on over 110% of set current Ir.
Number of poles 3 pole
Connection Front only
Mounting Fixed only
Category of use Type A according to IEC60947-2
Breaking capacity, Icu Ics = 50% of Icu
       
  Type ABS  
  220/240V 100kA  
  380/415V 65kA  
  440/460V 65kA  
  480/500V 50kA  
  600V 45kA  
       
       
Catalog No.    
  In

3-pole

Adjustable thermal range
    800A ABS803E 400 - 480 - 560 - 640 - 720 - 800A
    1200A ABS1203E 600 - 720 - 840 - 960 - 1080 - 1200A
         
         
  Optional accessories Auxiliary switch
      Alarm switch
      Shunt trip
      Undervoltage trip
      Insulation barrier
      (standard for line side only)
         
         
  Dimensions (mm)

3-pole

210 (W) x 580 (H) x 105 (D)

         

       

 