| Electronic trip |
| |
Rated current, In |
800, 1200A |
 |
Type of trip unit |
Electronic trip with LSIA configuration |
|
1. Long time pick-up, Ir |
(0.5-0.6-0.7-0.8-0.9-1.0) x In ..adjustable
via knob |
|
2. Short time pick-up, Im |
(2-3-4-5-6-8-10) x Ir ....adjustable via knob |
|
3. Short time delay, tm |
0.1 - 0.2 - 0.3 seconds ...adjustable |
|
Instantaneous pickup |
11 x In ...fixed |
|
4. Rated frequency |
50 - 60Hz selectable by switch on trip unit. |
|
5. Alarm |
Warning via LED flickering when the load |
| |
current is between 70 to 110% of set current
Ir. |
| |
LED stays on over 110% of set current Ir. |
|
Number of poles |
3 pole |
|
Connection |
Front only |
|
Mounting |
Fixed only |
|
Category of use |
Type A according to IEC60947-2 |
|
Breaking capacity, Icu |
Ics = 50%
of Icu |
| |
|
|
|
| |
Type |
ABS |
|
 |
|
220/240V |
100kA |
|
| |
380/415V |
65kA |
|
| |
440/460V |
65kA |
|
| |
480/500V |
50kA |
|
| |
600V |
45kA |
|
| |
|
|
|
| |
|
|
|
|
Catalog No. |
|
|
| |
In |
3-pole |
Adjustable thermal range |
| |
|
800A |
ABS803E |
400 - 480 - 560 - 640 - 720 - 800A |
| |
|
1200A |
ABS1203E |
600 - 720 - 840 - 960 - 1080 - 1200A |
| |
|
|
|
|
| |
|
|
|
|
| |
Optional accessories |
Auxiliary switch |
| |
|
|
Alarm switch |
| |
|
|
Shunt trip |
| |
|
|
Undervoltage trip |
| |
|
|
Insulation barrier |
| |
|
|
(standard for line side only) |
| |
|
|
|
|
| |
|
|
|
|
| |
Dimensions (mm) |
3-pole |
210 (W) x 580 (H) x 105 (D) |
| |
|
|
|
|
 |
|
 |
| |
|
|
|
 |