LG Adjustable MCCBs 800AF E-Trip
LG Industrial Systems
Benedikt Jager
Broyce Control
Controls Switchgear
Albright International UK
Vishay Germany
Rudolf
PFC Modules
Adjustable MCCBs Electronic Trip
GBN types
Page Links
Thermal-magnetic trip
Electronic trip
Auxiliaries
Manual Rotary Handles
Adjustable MCCBs Frame Size 800AF Electronic Trip
Electronic trip
Rated current, In
800A
Type of trip unit
Electronic trip with LSIA configuration
1.
Long time pick-up, Ir
(0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0) x In ... adjustment via knob
2.
Long time delay, tr
1.5 - 3 - 6 - 9 - 12 sec at 6 x Ir ...adjustable via knob
3.
Short time pick-up, Im
(2 - 3 - 4 - 5 - 6 - 8 - 10) x Ir ... adjustable via knob
4.
Short time delay, tm
0.1 - 0.2 - 0.3 sec ... adjustable
5.
Instantaneous pick-up
(1.5 - 3 - 6 - 8 - 10) x In ... adjustable via knob
6.
Rated frequency
50 to 60Hz selectable by switch on the trip unit
7.
Alarm
Warning via LED flickering when the load
current is between 70 to 115% of set current Ir.
LED stays on over 115% of set current Ir.
Number of poles
3 pole
Connection
Front only
Mounting
Fixed only
Category of use
Type A according to IEC947-2
Breaking capacity, Icu
Ics
=
50% of Icu
Type
GBN
220/240V
100kA
380/415V
50kA
440/460V
50kA
480/500V
45kA
600V
35kA
Catalog No.
In
3-pole
Adjustable thermal range
800A
GBN803E
400 - 480 - 560 - 640 - 720 - 800A
Optional accessories
Auxiliary switch
Alarm switch
Shunt trip
Undervoltage trip
Manual rotary handle
Terminal cover
Insulation barrier
(standard for line side only)
Dimensions (mm) 3-pole
210 (W) x 280 (H) x 110 (D)
LG Industrial Systems
Benedikt Jager
Broyce Control
Controls Switchgear
Albright International UK
Vishay Germany
Rudolf
PFC Modules