LG Air Breaker LBA-16C to LBA-32C Specifications
 









Ace-MEC Air circuit breaker
Specifications

 

Page Links

 
     
     
     
     

Types LBA-16C, LBA-20C, LBA-25C and LBA-32C

 

Type LBA-16C LBA-20C LBA-25C LBA-32C
Rated current (In max) (A) at 40°C 1600 2000 2500 3150
(3200)
 note (1)
Rated operating voltage (Ue) (V) 690 690 690 690
Rated insulation voltage

(Ui)

(V)

1000 1000 1000 1000
Frequency note (2) (Hz) 50/60 50/60 50/60 50/60
Number of poles (P) 3,4 3,4 3,4 3,4
Setting current (In)

     (A) Control trip relay (...x In Max)

1.0,0.9, 0.8, 0.7, 0.6, 0.5, 0.4 (7 steps)
Rated current of
neutral pole
(A) 1600 2000 2500 3200
Rated breaking
capacity
(Icu)
(Sym)
(kA)

KS C 8325 AC


DC

660V 50 65 65 65
600V 50 65 65 65
500V Under 65 85 85 85
250V note (3) 25 32 32 32
IEC 60947-2
AC
690V 50 65 65 65
600v 50 65 65 65
500V Under 65 85 85 85
Rated service breaking
capacity (Ics)
(kA) ...% x Icu 100 100 100 100
Rated making capacity
(Icm)
(peak)
(kA) KS C 8325
AC
660V 105 143 143 143
600V 105 143 143 143
500V Under 143 187 187 187
IEC 60947-2
AC
690V 105 143 143 143
600v 105 143 143 143
500V Under 143 187 187 187
Rated Short-time
capacity (Icw)
(kA) 1 sec 65 65 65 65
2 sec note (3) 60 65 65 65
3 sec note (3) 50 65 65 65
Operating time (ms) Maximum total breaking time 40 40 40 40
Closing time 80 80 80 80
Life cycle ACB (time) Mechanical Without maintenance 10000 10000 10000 10000
With maintenance 20000 20000 20000 20000
Electrical Without maintenance 3000 3000 3000 3000
With maintenance 5000 5000 5000 5000
ATS with
ACBs note(4
(time) Mechanical Without maintenance 10000 10000 10000 10000
Electrical Without maintenance 3000 3000 3000 3000
Draw-out type
Weight (3P/4P) (kg) Main Body
(with cradle)
Motor charging type 67/81 95/116 96/117 98/119
Manual charging type 64/78 92/113 93/114 95/116
Cradle only 26/30 35/43 35/43 36/44
Fixed Type
Weight (3P/4P) (kg)   Motor charging type 44/54 63/75 64/76 66/78
Manual charging type 41/51 60/72 61/73 63/75
Bus-bar Connection type Horizontal type Standard Standard Standard Standard
Vertical typenote(5 Option Option Option Option
Closing type Motor charging type Standard Standard Standard Standard
Manual charging type Option Option Option Option

External

Draw-out Type (mm) H:435, D:376 W(3P/4P) 338/423 473/603 473/603 473/603

dimension

Fixed Type

(mm)

H:410, D:285 W(3P/4P) 340/425 475/605 475/605 475/605
Note:
1 Rated current of IEC standard.
2 Trip relay is divided into 50Hz and 60Hz. Please be careful to order correct frequency.
3 Reference rating.
4 Ace-MEC ACB with interlock device can be a substitute for ATS.
5 For main body, only horizontal type is available. For cradle, vertical type is optional.

 