LG DMPR Ordering Code
 







Ordering Codes
Digital EMPR

Page Links    
     
     
   
   
     
     
       

  Ordering Codes For DMP Series

 

Example Code for DMP06-SEZ

                     
  Current Setting
Range
Wiring Method
 
Type
 
Option
 

Operating Power
 

 
06 0.5 ~ 6A
60 5 ~ 60A
S Screw
T Tunnel
- Unit
E Extension
Z Ground fault
I Short circuit
220 AC220V
110 AC110V

 

  • The standard length of a extension cable is 1 meter.
    2m, 4m cable length is optional.
  • For ground fault protection, ZCT (30Ø, 50Ø, 65Ø, 80Ø)
    made by LG is optionally required.
(1.) Detach the screw terminal  

Remove the 3 screws either in the line side or the load side and pull out the bus bar.
If you remove the screw terminal, you can use it as tunnel type digital EMPR, assemble it to the opposite sequence.
(2.) Select the ground fault sensitive current.

Sensitive current
(mA)

Dip Switch

1 2 3 4
100 O O O O
200 1 O O O
500 0 1 O O
1000 O O 1 O
1500 O O O 1
2000 O O 1 1
2500 1 1 1 1

Note: High sensitive current (30 ~ 300mA)
         is optional.

 

 

LG Industrial Systems Benedikt Jager Broyce Control Controls Switchgear
Albright International UK Vishay Germany Rudolf PFC Modules