Ordering Codes
Digital
EMPR |
Ordering Codes For DMP Series
- The standard length of a extension cable is 1 meter.
2m, 4m cable length is optional.
- For ground fault protection, ZCT (30Ø, 50Ø, 65Ø,
80Ø)
made by LG is optionally required.
|
| (1.) Detach the screw terminal |
|
|
 |
Remove the 3 screws either in the line side or
the load side and pull out the bus bar.
If you remove the screw terminal, you can use it as tunnel type digital
EMPR, assemble it to the opposite sequence. |
| (2.) Select the ground fault sensitive
current. |
 |
|
Sensitive current
(mA) |
Dip Switch |
|
1 |
2 |
3 |
4 |
|
100 |
O |
O |
O |
O |
|
200 |
1 |
O |
O |
O |
|
500 |
0 |
1 |
O |
O |
|
1000 |
O |
O |
1 |
O |
|
1500 |
O |
O |
O |
1 |
|
2000 |
O |
O |
1 |
1 |
|
2500 |
1 |
1 |
1 |
1 |
|
Note: High sensitive current (30
~ 300mA)
is optional. |
|
|
|
 |
|