LG DMPR Setting 1
 







D-EMPR Setting
Digital EMPR

Page Links

  Page Bookmarks
   
   
 
  Links To
   
  Link Back
     

Digital EMPR Settings 3 and 4

 

  Alert Function  













 
5. Alt is the alert setting mode. It displays the load rate of the current setting value by the bar LED (60 ~ 110%).
- If the current is higher than the setting value, the bar LED is switched ON and OFF and the AL relay (07-08) make and close and open in 1 second intervals until the EMPR is tripped.
(Pre-alarm function)
-If the 5. Alt mode is set to OFF, the AL relay makes and close after the EMPR is tripped (Normally open contact).

6. To finish the settings you have to press the "Sel" button in the Sto mode.

Alarm signal (Alert function)



3. Adjust the operating time by the time control knob
 

 

 








 
Inverse time characteristics
  1. Select the inverse time in the 1. CHA mode, the default operating time is 600% of the rated current.
  2. The setting range of the operating time is 0 ~ 60 seconds. Set the time by considering the motor start time.
  3. When it is over the setting time, the EMPR operate in accordance with the hot curve. (see Inverse time characteristic graph)
  Definite time characteristics
  1. Select the definite in the 1. CHA mode, it is operated by the definite time characteristics.
  2. D-time means the time that delays the operating time when the motor is starting.
  3. The setting range of the operating time is 0 ~ 60 seconds. Set the time by considering the motor start time.
  4. Set the 0-time at the setting mode 2. dEF and the range is 0 ~ 30 seconds.
4. Adjust the operating current by the current knob
   
  1. Set the operating current based on the rated current that is described in the name plate. Generally set the 110 ~ 115% of the real load current in the normal load condition.
  2. There are 2 CT types according to the current range (0.6 / 60). When you use the external CT you can see the real current by setting the CT ratio (in DMP60CT types the default CT ratio is 10:1).
  3. You can easily set the current value by referring to the load rate which is displayed on the bar-graph (approx. 90% load rate).