Model No. |
DMP06-S |
DMP60-S |
DMP06-T |
DMP60-T |
|
Wiring |
Screw type |
Tunnel type |
|
Panel mount |
Unit |
Operating time
|
Select either reverse time
characteristics or definite time characteristics |
|
Protection |
|
|
|
|
|
Over current |
|
According to the setting time |
|
|
Phase failure |
|
3 seconds |
|
Reverse phase |
|
Within 0.1second |
|
Asymmetry |
|
5 seconds |
|
Stall |
|
5 seconds |
|
Lock |
|
Within 0.5 second |
|
Under current |
|
3 seconds |
|
Ground fault |
|
Within 0.05 ~ 1 second. Selectable (0.05 ~ 1.0 second) |
|
Short circuit |
(note²) |
Within 50ms |
|
Alarm |
Variable (60 ~ 110% of the setting current) |
|
Current setting range (Amps) |
0.5 ~ 6 |
5 ~ 60 |
0.5 ~ 6 |
5 ~ 60 |
|
Motor capacity |
220 ~ 240V |
0.09 ~ 0.75 |
1.1 ~ 11 |
0.09 ~ 0.75 |
1.1 ~ 11 |
|
|
|
380 ~ 440V |
0.12 ~ 1.5 |
2.2 ~ 22 |
0.09 ~ 1.5 |
2.2 ~ 22 |
|
Time setting |
Definite time |
Delay in starting |
0 ~ 60 seconds |
|
|
|
Delay in operating |
0 ~ 30 seconds |
|
Inverse time |
|
0 ~ 60 seconds |
|
Reset |
|
Manual reset |
|
Tolerance |
Current |
|
±5% |
|
|
Time |
|
±5% (or ± 0.5sec) |
|
Operating power |
Voltage (note³) |
AC 190 ~ 250V |
|
|
|
Frequency (note³) |
60Hz (50Hz) |
|
Aux. contact |
|
|
|
OL |
2-SPST |
3A/250V AC Resistive load |
|
AL |
SPST |
3A/250V AC Resistive load |
|
Insulation resistance |
|
Over DC 500V 100MΩ |
|
Surge impulse voltage (IEC1000-4-5) |
1.2 X 50μS 6kV (Apply standard wave form) |
|
Fast transient burst (IEC1000-4-4) |
2.5kV/5min |
|
Environment |
Temperature |
Operation |
-25°C ~ 70°C |
|
|
|
Storage |
-30°C ~ 80°C |
|
Humidity |
|
-30% ~ 90%RH (No freezing) |
|
Display |
7-Segment |
|
3-phase current, cause of a fault |
|
|
Bar-graph |
|
60% ~ 110% of real load current |
|
Mounting type |
|
35mm DIN-rail/Panel |
Note 1.) In extension type, the digital EMPR is calibrated by combining
the display part and the main-body. Do not order the 'Display and the Main
body' separately using different part numbers they must be ordered as a
complete item so they can be calibrated.
|
Note 2.) Instantaneous short
circuit protection is optional.
|
| Note 3.) Operational voltage of AC
110V and 50Hz is optional. |