Moulded
Case Circuit Breaker (MCCBs)
Types 400AF Specifications |
MCCBs
Specification for
Frame Size 400AF
|
Frame Size |
400AF |
| Frame type (AF) |
|
ABE |
ABS |
ABH |
ABL |
GBN |
| Breaking capacity (kA), Icu at 415V AC |
25 |
35 |
50 |
65 |
35 |
| Number of poles |
2,3,4 |
2,3,4 |
2,3,4 |
2,3,4 |
3 |
| Type |
|
2 pole |
ABE402a |
ABS402a |
ABH402a |
ABL402a |
|
|
|
3 pole |
ABE403a |
ABS403a |
ABH403a |
ABL403a |
GBN403E |
|
|
4 pole |
ABE404a |
ABS404a |
ABH404a |
ABL404a |
|
| Rated current (A) |
|
250, 300, 350, 400 |
400 |
| In at 40°C |
|
Interchangeable via rating plug between |
|
|
|
|
250 and 300 |
Electronically |
|
|
|
350 and 400 |
adjustable; |
|
|
|
|
|
(0.5-0, 6-0, 7-0, 8-0, 9-1.0) x In |
|
| Technical data conforming to IEC/EN60947-2 |
| Rated operational voltage |
600 |
600 |
600 |
600 |
600 |
| (V), Ue(50/60Hz) |
|
|
|
|
|
| Rated operational voltage (V), Ue(DC) |
250 |
250 |
250 |
250 |
- |
| Rated insulation voltage (V), Ui (50/60Hz) |
690 |
690 |
690 |
690 |
690 |
| Rated impulse withstand voltage |
|
|
|
|
|
| (kV), Uimp |
6 |
6 |
6 |
6 |
6 |
| Ultimate breaking capacity (kA), Icu |
|
|
|
|
|
|
AC |
220/240V |
35 |
50 |
85 |
125 |
50 |
|
50/60Hz |
380/415V |
25 |
35 |
50 |
65 |
35 |
|
|
440/460V |
25 |
35 |
50 |
65 |
35 |
|
|
480/500V |
18 |
25 |
35 |
50 |
25 |
|
|
600V |
18 |
22 |
30 |
35 |
22 |
|
DC |
125V |
20 |
30 |
50 |
60 |
- |
|
|
250V |
10 |
20 |
40 |
40 |
- |
| Service breaking capacity (%Icu), Ics |
50 |
50 |
50 |
50 |
50 |
| Category of use |
A |
A |
A |
A |
A |
| Endurance |
mechanical |
4,000 |
4,000 |
4,000 |
4,000 |
4,000 |
| (number of operations) |
|
|
|
|
|
|
|
electrical |
1,000 |
1,000 |
1,000 |
1,000 |
1,000 |
| Type of trip unit |
|
|
|
|
|
| Thermal-magnetic release |
fixed |
fixed |
fixed |
fixed |
|
| Electronic release |
|
|
|
|
LSIA
configuration |
| Pre-alarm via LED |
|
|
|
|
|
| Hydraulic-magnetic release |
|
|
|
|
|
Magnetic release only without thermal
trip |
|
|
|
 |
|
| Earth leakage protection |
|
|
|
|
|
|
|
for 3 pole |
 |
 |
 |
 |
|
|
|
|
| Accessories |
| Electrical auxiliaries |
|
|
|
|
|
|
|
auxiliary switch |
 |
 |
 |
 |
 |
|
|
alarm switch |
 |
 |
 |
 |
 |
|
|
shunt trip |
 |
 |
 |
 |
 |
|
|
undervoltage trip |
 |
 |
 |
 |
 |
| External accessories |
|
|
|
|
|
|
|
manual rotary handle |
 |
 |
 |
 |
 |
|
|
terminal cover |
 |
 |
 |
 |
 |
|
|
insulation barrier |
 |
 |
 |
 |
 |
|
|
rear connection |
- |
- |
- |
- |
- |
|
|
mechanical interlock |
|
 |
 |
 |
 |
|
|
remote control |
- |
- |
- |
- |
- |
| Dimensions (mm) |
3 pole breaker |
140(W) x 257(H) x 110(D) |
| Weight (kg) |
2 pole |
5.2 |
5.2 |
5.2 |
5.2 |
5.2 |
|
|
3 pole |
6.2 |
6.2 |
6.2 |
6.2 |
6.2 |
|
|
4 pole |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
| Note:
applicable or available