MCCBs Specifications for Frame Size 800AF

250AF 400AF 800AF 1200AF

 

Frame Size

800AF

Frame type (AF) ABE ABS ABL GBN
Breaking capacity (kA), Icu at 415V AC 35 50 65 50
Number of poles 2,3,4 2,3,4 2,3,4 3
Type 2 pole ABE802a ABS802a ABL802a
3 pole ABE803a ABS803a ABL803a GBN803E
4 pole ABE804a ABS804a ABL804a
Rated current (A) 500, 600, 630, 700, 800 800
In at 40°C Interchangeable via rating plug between Electronically
500 and 600 adjustable;
700 and 800 (0.5-0, 6-0, 7-0, 8-0,
9-1.0) x In
Technical data conforming to IEC/EN60947-2
Rated operational voltage
(V), Ue(50/60Hz) 600 600 600 600
Rated operational voltage (V), Ue(DC) 250 250 250 -
Rated insulation voltage (V), Ui (50/60Hz) 690 690 690 690
Rated impulse withstand voltage
(kV), Uimp 6 6 6 6
Ultimate breaking capacity (kA), Icu
AC 220/240V 50 100 125 100
50/60Hz 380/415V 35 50 65 50
440/460V 35 50 65 50
480/500V 25 35 50 45
600V 22 30 35 35
DC 125V 30 50 60 -
250V 20 40 40 -
Service breaking capacity (%Icu), Ics
Category of use A A A A
Endurance mechanical 4,000 4,000 4,000 2,500
(number of operations)
electrical 1,000 1,000 1,000 500
Type of trip unit
Thermal-magnetic release fixed fixed fixed
Electronic release       LSIA
configuration
 
Pre-alarm via LED
Hydraulic-magnetic release
Magnetic release only without thermal
trip
   
   
Earth leakage protection
for 3 pole
Accessories
Electrical auxiliaries
auxiliary switch
alarm switch
shunt trip
undervoltage trip
External accessories
manual rotary handle
terminal cover
insulation barrier
rear connection - - - -
mechanical interlock
remote control - - - -
Dimensions (mm) 3 pole breaker 210 (W) x 280 (H) x 110 (D)
Weight (kg) 2 pole 11 11 11 11
3 pole 11.5 11.5 11.5 11.5
4 pole 18.2 18.2 18.2 18.2