Moulded
Case Circuit Breaker (MCCBs)
Types 800AF Specifications |
MCCBs
Specifications for
Frame Size 800AF
|
Frame Size |
800AF |
|
Frame type (AF) |
|
ABE |
ABS |
ABL |
GBN |
|
|
Breaking capacity (kA), Icu at 415V AC |
35 |
50 |
65 |
50 |
|
|
Number of poles |
2,3,4 |
2,3,4 |
2,3,4 |
3 |
|
|
Type |
|
2 pole |
ABE802a |
ABS802a |
ABL802a |
|
|
|
|
3 pole |
ABE803a |
ABS803a |
ABL803a |
GBN803E |
|
|
|
4 pole |
ABE804a |
ABS804a |
ABL804a |
|
|
|
Rated current (A) |
|
500, 600, 630, 700, 800 |
800 |
|
|
In at 40°C |
|
Interchangeable via rating plug between |
Electronically |
|
|
|
|
500 and 600 |
adjustable; |
|
|
|
|
700 and 800 |
(0.5-0, 6-0, 7-0, 8-0, |
|
|
|
|
|
|
9-1.0) x In |
|
|
|
|
Technical data conforming to IEC/EN60947-2 |
|
Rated operational voltage |
|
|
|
|
|
|
(V), Ue(50/60Hz) |
600 |
600 |
600 |
600 |
|
|
Rated operational voltage (V), Ue(DC) |
250 |
250 |
250 |
- |
|
|
Rated insulation voltage (V), Ui (50/60Hz) |
690 |
690 |
690 |
690 |
|
|
Rated impulse withstand voltage |
|
|
|
|
|
|
(kV), Uimp |
6 |
6 |
6 |
6 |
|
|
Ultimate breaking capacity (kA), Icu |
|
|
|
|
|
|
AC |
220/240V |
50 |
100 |
125 |
100 |
|
|
50/60Hz |
380/415V |
35 |
50 |
65 |
50 |
|
|
|
440/460V |
35 |
50 |
65 |
50 |
|
|
|
480/500V |
25 |
35 |
50 |
45 |
|
|
|
600V |
22 |
30 |
35 |
35 |
|
|
DC |
125V |
30 |
50 |
60 |
- |
|
|
|
250V |
20 |
40 |
40 |
- |
|
|
Service breaking capacity (%Icu), Ics |
|
|
|
|
|
|
Category of use |
A |
A |
A |
A |
|
|
Endurance |
mechanical |
4,000 |
4,000 |
4,000 |
2,500 |
|
|
(number of operations) |
|
|
|
|
|
|
|
electrical |
1,000 |
1,000 |
1,000 |
500 |
|
|
|
|
|
|
|
|
|
|
Type of trip unit |
|
Thermal-magnetic release |
fixed |
fixed |
fixed |
|
|
|
Electronic release |
|
|
|
LSIA
configuration |
|
|
Pre-alarm via LED |
|
|
|
|
|
|
Hydraulic-magnetic release |
|
|
|
|
|
Magnetic release only without thermal
trip |
|
|
 |
|
|
|
Earth leakage protection |
|
|
|
|
|
|
|
for 3 pole |
 |
 |
 |
|
|
|
|
|
|
Accessories |
|
Electrical auxiliaries |
|
|
|
|
|
|
|
auxiliary switch |
 |
 |
 |
 |
|
|
|
alarm switch |
 |
 |
 |
 |
|
|
|
shunt trip |
 |
 |
 |
 |
|
|
|
undervoltage trip |
 |
 |
 |
 |
|
|
External accessories |
|
|
|
|
|
|
|
manual rotary handle |
 |
 |
 |
 |
|
|
|
terminal cover |
 |
 |
 |
 |
|
|
|
insulation barrier |
 |
 |
 |
 |
|
|
|
rear connection |
- |
- |
- |
- |
|
|
|
mechanical interlock |
 |
 |
 |
 |
|
|
|
remote control |
- |
- |
- |
- |
|
| Dimensions (mm) |
3 pole breaker |
210 (W) x 280 (H) x 110 (D) |
|
| Weight (kg) |
2 pole |
11 |
11 |
11 |
11 |
|
|
|
3 pole |
11.5 |
11.5 |
11.5 |
11.5 |
|
|
|
4 pole |
18.2 |
18.2 |
18.2 |
18.2 |
|
| Note:
applicable or available
available as a separate breaker |
|
 |
|