| Thermal magnetic trip |
 |
Rated
current, In |
1000, 1200A |
| Type of trip
unit |
Fixed thermal and adjustable
magnetic |
| Frequency |
50Hz or 60Hz (not common use) |
| Number of
poles |
3, 4 pole |
| Connection |
Front (standard) |
| Mounting |
Fixed only |
| Category of
use |
Type A according to IEC60947-2 |
| Breaking
capacity, Icu |
Ics =
50% of Icu |
| |
Type |
ABS |
|
|
| |
220/240V |
100kA |
|
|
| |
380/415V |
65kA |
|
|
| |
440/460V |
65kA |
|
|
| |
480/500V |
50kA |
|
|
| |
600V |
45kA |
|
|
|
|
|
|
|
|
|
|
|
|
| Catalog No. |
For 50Hz |
|
|
|
|
In |
3-pole |
4-pole |
Magnetic adjustable range |
|
|
1000A |
ABS1003/50 |
ABS1004/50 |
3000 to 6000A |
|
 |
|
1200A |
ABS1203/50 |
ABS1204/50 |
3000 to 7200A |
|
|
|
|
|
|
|
For 60Hz |
|
|
|
In |
3-pole |
4-pole |
Magnetic adjustable range |
|
1000A |
ABS1003/60 |
ABS1004/60 |
3000 to 6000A |
|
1200A |
ABS1203/60 |
ABS1204/60 |
3000 to 7200A |
|
|
|
|
|
|
|
|
|
|
|
|
Optional
accessories |
Auxiliary switch |
|
|
|
|
Alarm switch |
|
|
|
|
Shunt trip |
|
|
|
|
Undervoltage trip |
|
|
|
|
Insulation barrier |
|
|
|
|
(standard for line side only) |
|
|
|
|
|
|
|
|
Dimensions |
3 pole |
210 (W) x 580 (H) x 105 (D) |
|
|
(mm) |
4 pole |
280 (W) x 580 (H) x 105 (D) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- MCCB with reference temperature 50°C is available
on request.
- MCCB with electronic trip unit
|
|
|
|
|
|
 |