Rated current, In |
250, 300, 350, 400Amp |
| Type of trip unit |
Interchangeable thermal and fixed magnetic |
| Thermal current |
Interchangeable by rating plugs |
| Magnetic trip |
(9 to 15) x In ... non-adjustable |
| |
Magnetic adjustable types are optional |
| Number of poles |
2, 3, and 4 pole |
| Connection |
Front (standard) |
| |
Rear (optional) |
| Mounting |
Fixed only |
| Category of use |
Type A according to IEC947-2 |
| Breaking capacity, Icu |
Ics = 50%
of Icu |
| |
Type |
ABE |
ABS |
ABH |
ABL |
| |
220/240V |
35kA |
50kA |
85kA |
125kA |
| |
380/415V |
25kA |
35kA |
50kA |
65kA |
| |
440/460V |
25kA |
35kA |
50kA |
65kA |
| |
480/500V |
18kA |
25kA |
35kA |
50kA |
| |
600V |
18kA |
22kA |
30kA |
35kA |
| |
|
|
|
|
|
|
| |
Catalog No. |
for 25kA at 415V ...
TypeABE |
| |
|
|
|
|
|
Interchangeable |
| |
|
In |
2-pole |
3-pole |
4-pole |
rating plug |
Earth leakage
circuit breaker

Types EBE/S/H/L403
physically
interchangeable
with MCCBs |
|
250A |
ABE402a/250 |
ABE403a/250 |
ABE404a/250 |
300A |
| |
300A |
ABE402a/300 |
ABE403a/300 |
ABE404a/300 |
250A |
| |
350A |
ABE402a/350 |
ABE403a/350 |
ABE404a/350 |
400A |
| |
400A |
ABE402a/400 |
ABE403a/400 |
ABE404a/400 |
350A |
| |
|
|
|
|
|
| |
|
for 35kA at 415V ...
TypeABS |
| |
|
|
|
|
Interchangeable |
| |
In |
2-pole |
3-pole |
4-pole |
rating plug |
| |
250A |
ABS402a/250 |
ABS403a/250 |
ABS404a/250 |
300A |
| |
300A |
ABS402a/300 |
ABS403a/300 |
ABS404a/300 |
250A |
| |
350A |
ABS402a/350 |
ABS403a/350 |
ABS404a/350 |
400A |
| |
400A |
ABS402a/400 |
ABS403a/400 |
ABS404a/400 |
350A |
| |
|
|
|
|
|
| |
|
|
for 50kA at 415V ...
TypeABH |
| |
|
|
|
|
|
Interchangeable |
| |
|
In |
2-pole |
3-pole |
4-pole |
rating plug |
| Optional |
|
250A |
ABH402a/250 |
ABH403a/250 |
ABH404a/250 |
300A |
|
Accessories |
|
300A |
ABH402a/300 |
ABH403a/300 |
ABH404a/300 |
250A |
|
Auxiliary switch |
|
350A |
ABH402a/350 |
ABH403a/350 |
ABH404a/350 |
400A |
| Alarm switch |
|
400A |
ABH402a/400 |
ABH403a/400 |
ABH404a/400 |
350A |
| Shunt trip |
|
|
|
|
|
|
| Undervoltage trip |
|
|
for 65kA at 415V ...
TypeABL |
| Manual rotary handle |
|
|
|
|
Interchangeable |
| Terminal cover |
|
In |
2-pole |
3-pole |
4-pole |
rating plug |
| Mechanical interlock |
250A |
ABL402a/250 |
ABL403a/250 |
ABL404a/250 |
300A |
| Rear connection unit |
300A |
ABL402a/300 |
ABL403a/300 |
ABL404a/300 |
250A |
| Insulation barrier |
|
350A |
ABL402a/350 |
ABL403a/350 |
ABL404a/350 |
400A |
| (standard for line side only) |
400A |
ABL402a/400 |
ABL403a/400 |
ABL404a/400 |
350A |
| |
|
|
|
|
|
|
|
Dimensions (mm) |
2/3 pole |
140 (W) x 257 (H) x 110 (D) |
|
|
4 pole |
185 (W) x 257 (H) x 110 (D) |
|
| |
|
|
|
|
 |
|
|
|
|
|
|
| |
|
- MCCB with reference temperature 50°C is available
on request.
-
MCCB with electronic trip unit
|
 |