LG Non-Adjustable MCCBs 800AF
s
 







Non-adjustable MCCBs Breaker size 800AF
Page Links Interchangeable
Thermal and fixed magnetic trip
Auxiliaries
   
     
  Fixed Thermal and Adjustable Magnetic trip
       
     

Non-adjustable MCCB Size 800AF

 

Rated current, In 500, 600, 700 800Amp
Type of trip unit Interchangeable thermal and fixed magnetic
Thermal current Interchangeable by rating plugs
Magnetic trip (9 to 15) x In ... non-adjustable
  Magnetic adjustable types are optional
Number of poles 2, 3, and 4 pole
Connection Front (standard)
  Rear (optional)
Mounting Fixed only
Category of use Type A according to IEC947-2
Breaking capacity, Icu Ics = 50% of Icu
  Type

ABE

ABS ABL  
  220/240V 50kA 85kA 125kA  
  380/415V 35kA 50kA 65kA  
  440/460V 35kA 50kA 65kA  
  480/500V 25kA 35kA 50kA  
  600V 22kA 30kA 35kA  
             
  Catalog No.

for 35kA at 415V ... TypeABE

           

Interchangeable

    In 2-pole 3-pole 4-pole

rating plug

Earth leakage
circuit breaker


Types EBE/S/L803
physically
interchangeable
with MCCBs

  500A ABE802a/500 ABE803a/500 ABE804a/500 600A
  600A ABE802a/600 ABE803a/600 ABE804a/600 500A
  630A ABE802a/630 ABE803a/630 ABE804a/630  
  700A ABE802a/700 ABE803a/700 ABE804a/700 800A
  800A ABE802a/800 ABE803a/800 ABE804a/800 700A
           
   

for 50kA at 415V ... TypeABS

         

Interchangeable

  In 2-pole 3-pole 4-pole

rating plug

  500A ABS802a/500 ABS803a/500 ABS804a/500 600A
  600A ABS802a/600 ABS803a/600 ABS804a/600 500A
  630A ABS802a/630 ABS803a/630 ABS804a/630  
  700A ABS802a/700 ABS803a/700 ABS804a/700 800A
    800A ABS802a/800 ABS803a/800 ABS804a/800 700A
Optional            

Accessories

   

for 65kA at 415V ... TypeABL

Auxiliary switch           Interchangeable
Alarm switch   In 2-pole 3-pole 4-pole

rating plug

Shunt trip   500A ABL402a/500 ABL403a/500 ABL404a/500 600A
Undervoltage trip   600A ABL402a/600 ABL403a/600 ABL404a/600 500A
Manual rotary handle 630A ABL402a/630 ABL403a/630 ABL404a/630  
Terminal cover   700A ABL402a/700 ABL403a/700 ABL404a/700 800A
Mechanical interlock 800A ABL402a/800 ABL403a/800 ABL404a/800 700A
Rear connection unit          
Insulation barrier            
(standard for line side only)          
             
Dimensions (mm)

2/3 pole

210 (W) x 280 (H) x 110 (D)    

4 pole

280 (W) x 280 (H) x 110 (D)  
   

 

 
  • MCCB with reference temperature 50°C is available on request.
  • MCCB with electronic trip unit

 

 